BASIC TECHNICAL PARAMETERS
Parameters Value
Rated voltage, kV 6
The highest operating voltage, kV 7,2
Rated current, A 1 600; 2 000
Rated breaking current, kA 40
Thermal withstand current, kA (3 s) 40
Electrodynamic stability current, kA 128
Full shutdown time, ms, no more 70
Own turn-on time, ms, no more 120
Own shutdown time, ms, no more 35–55
Mechanical life, VO cycles 30 000
Switching resource at rated currents, VO cycles 30 000
Switching resource at rated breaking currents, VO cycles 40
Weight, kg 162